Electrical Engineering Calculation Submittal
Circuit Breaker Sizing Calculator
Category: Power Systems & Protection
Generated: Oct 24, 2026 • voltbase.pro
Project: ___________________
Tag / Location: ___________________
Prepared By: ___________________
Date: ___________________
Power Systems & ProtectionPure Browser Calculation • Zero Latency

Circuit Breaker Sizing Calculator

Calculate standard circuit breaker ampere ratings applying the continuous load 80% / 125% rule.

A

e.g. Water heaters, EV chargers, continuous lighting

A

Intermittent loads (e.g. microwave, garbage disposal)

Circuit Breaker Recommendation

Recommended Standard Breaker
20 Amps

Minimum required circuit ampacity: 20 A

Continuous Load Component
16 A (Factored: 20.00 A)
Non-Continuous Component
0 A
Electrical Code Notice
Circuit breaker sizing must always protect the smallest connected conductor ampacity and comply with governing electrical codes (such as NEC Article 240 / IEC 60364). Motor circuits, HVAC compressors (MCA/MOP), and transformer inrush require specialized overcurrent calculations. Verify all installations with a licensed electrical contractor.

Step-by-Step Engineering Calculation

  1. 1Non-continuous load: Inon-cont=0 AI_{\text{non-cont}} = 0\text{ A}Inon-cont​=0 A
  2. 2Continuous load (runs ≥3\ge 3≥3 hrs): Icont=16 A×125%=20.00 AI_{\text{cont}} = 16\text{ A} \times 125\% = 20.00\text{ A}Icont​=16 A×125%=20.00 A
  3. 3Minimum OCPD Ampacity: Imin=20.00 AI_{\text{min}} = 20.00\text{ A}Imin​=20.00 A
  4. 4Standard commercial breaker rating: 20 A (NEC 240.6(A))

Formula & Theory

Min Breaker Rating = Non-Continuous Amps + (Continuous Amps × 125%)

Computes minimum required overcurrent protection device (OCPD) ampere ratings for branch and feeder circuits.

Variable Definitions
I_cont:
Continuous Load (Amperes (A)) – Load sustained for 3+ continuous hours
I_noncont:
Non-Continuous Load (Amperes (A)) – Intermittent branch load
Rating:
Standard Breaker (Amperes (A)) – Next standard OCPD commercial size

Worked Engineering Example

Commercial Continuous Lighting Circuit

A 16A continuous commercial LED lighting load.

Inputs:
  • Continuous Load: 16 A
Result: Min Ampacity = 20.00 A | Standard Breaker = 20 A (12 AWG Copper)

Key Assumptions

  • •Standard 80%-rated commercial molded-case circuit breaker (MCCB).

Limitations & Safety Scope

  • •Breakers must be matched to conductor thermal ampacity ratings. 100%-rated breakers require listed assemblies and special considerations.
VoltBase Pro (voltbase.pro) • Electrical Engineering Reference & Calculation Submittal
Governing Reference: NEC 2023 / IEEE Standard Baseline
Calculated By: __________________________
Reviewed By: __________________________
Approved / Stamped: __________________________

Frequently Asked Questions

What is the 80% continuous breaker rule?

Under NEC Section 210.20, standard circuit breakers may only carry up to 80% of their nameplate rating continuously (for 3 hours or longer). Alternatively, continuous loads must be multiplied by 125% when sizing the breaker.

Related Calculators & Engineering Tools

Wire Size Calculator
Fuse Size Calculator
Voltage Drop Calculator

Educational & Reference Notice: This calculator provides technical estimates based on standard physical formulas. Actual electrical installation, protective device sizing, and conductor selection must be verified against the applicable electrical code (NEC, IEC, CEC) by a licensed electrician or qualified professional engineer.

VoltBasePRO

Fast, practical electrical calculators, conversions, engineering charts, and technical reference tools.

Free Engineering Utilities

Calculators

  • Ohm's Law
  • Voltage Drop
  • Wire Sizing
  • Battery Runtime
  • Solar Array Sizing
  • Breaker Sizing
  • View All 20+ →

Converters & Charts

  • AWG to mm²
  • Watts to Amps
  • kW to HP
  • AWG Wire Table
  • Battery SoC Chart
  • Resistor Color Code

Reference & Guides

  • All Articles & Guides →
  • Master Formulas
  • Grounding vs Bonding
  • 3-Phase Motor Sizing
  • Transformer Sizing
  • Conduit Fill Guide
  • Unit Converter Tool

Platform & Standards

  • About VoltBase Pro
  • Editorial Guidelines
  • Calculation Methodology
  • Engineering Disclaimer
  • Contact & Peer Review
  • Privacy Policy
  • Terms of Use
  • HTML Sitemap

Engineering Disclaimer: Calculations, estimations, formulas, and charts provided on VoltBase Pro are intended solely for educational, reference, and informational purposes. Real-world electrical installations must comply with local electrical codes (e.g. NEC, IEC, CEC) and should always be verified by a licensed electrician or professional electrical engineer.

© 2026 VoltBase Pro. All rights reserved.

Calculated in your browser. Verified against NEC 2023 tables.