Wire Size Calculator (AWG & mm²)
Category: Wire & Cable
Generated: Oct 24, 2026 • voltbase.pro
Project: ___________________
Tag / Location: ___________________
Prepared By: ___________________
Date: ___________________
Wire & CablePure Browser Calculation • Zero Latency

Wire Size Calculator (AWG & mm²)

Calculate recommended minimum conductor gauge and cross-sectional area to keep voltage drop within allowable limits.

V
A
°C

For NEC 310.15(B)(1) correction. 30°C is the table baseline.

Ampacity follows the NEC procedure: Table 310.16 ampacity corrected for ambient temperature and conductor count, capped by the termination rating and the 240.4(D) small-conductor limits, then checked against your voltage-drop target. For continuous loads, enter the load current multiplied by 1.25.

Recommended Conductor Gauge

Recommended AWG Size
10 AWG

Nominal Area: 5.26 mm² (drop alone would need 3.99 mm²)

Allowable Ampacity (Derated)
30A

Table 310.16 ampacity × 1 ambient × 1 conductor-count, capped by termination rating

Estimated Voltage Drop
2.7338 V (2.2781%)
Voltage at Load
117.266V
Target Max Allowed Drop
3.6V
Sizing Scope Notice
Selection follows the NEC procedure: Table 310.16 ampacity with 310.15(B)(1) ambient correction and 310.15(C)(1) conductor-count adjustment, capped by the 110.14(C) termination rating and 240.4(D) small-conductor limits, plus a voltage-drop check using Chapter 9 Table 8 resistance at 75 C. For continuous loads, size conductors and overcurrent devices at 125% of the continuous portion (enter the factored current). Always verify the final installation against the adopted code edition and the AHJ.

Step-by-Step Engineering Calculation

  1. 1Load: I=15 AI = 15\text{ A}I=15 A at 120 V120\text{ V}120 V, one-way length L=75.0 ftL = 75.0\text{ ft}L=75.0 ft, COPPER conductors.
  2. 2Ampacity derating (NEC 310.15): ambient 30°C correction Famb=1F_{\text{amb}} = 1Famb​=1 (90°C column) × conductor-count adjustment Fccc=1F_{\text{ccc}} = 1Fccc​=1 (3 current-carrying) = combined factor 1.000\mathbf{1.000}1.000.
  3. 3Termination limit (NEC 110.14(C)): allowable ampacity is capped at the 75°C column of Table 310.16, and at the NEC 240.4(D) small-conductor limits where they apply.
  4. 4Voltage drop limit: 3% of 120 V=3.600 V3\%\text{ of }120\text{ V} = \mathbf{3.600\text{ V}}3% of 120 V=3.600 V, checked with NEC Chapter 9 Table 8 resistance at 75°C. (Drop alone would need at least 3.99 mm².)
  5. 5Selected conductor: 10 AWG (5.26 mm²). Allowable ampacity after derating and caps: 30.0 A≥15 A\mathbf{30.0\text{ A}} \ge 15\text{ A}30.0 A≥15 A ✓. Actual voltage drop: 2.73 V\mathbf{2.73\text{ V}}2.73 V (2.28%) ✓.
  6. 6Voltage at load: Vload=120 V−2.73 V=117.27 VV_{\text{load}} = 120\text{ V} - 2.73\text{ V} = \mathbf{117.27\text{ V}}Vload​=120 V−2.73 V=117.27 V

Formula & Theory

A_min = (Multiplier × ρ × L × I) / ΔV_max

Calculates the minimum required cross-sectional conductor area (mm² and AWG) to ensure circuit voltage drop stays below the target threshold.

Variable Definitions
A_min:
Minimum Area (mm² / kcmil) – Minimum required cross-sectional conductor area
AWG:
Gauge (AWG) – Recommended American Wire Gauge
ΔV_max:
Max Drop (Volts (V)) – Maximum allowable voltage drop

Worked Engineering Example

24V Off-Grid Solar Battery Cable Run

A 24V DC inverter circuit pulling 40A over 20 feet with a 2% allowed voltage drop.

Inputs:
  • Voltage: 24 V
  • Current: 40 A
  • Length: 20 ft
  • Max Drop: 2%
Result: Recommended: 4 AWG Copper (Actual Drop: 1.66%, 0.40V)

Key Assumptions

  • •Pure conductor resistance sizing based on allowed voltage drop.

Limitations & Safety Scope

  • •Thermal ampacity derating (insulation class 60°C/75°C/90°C, ambient temperature, conduit fill) must be verified against NEC Article 310 or IEC 60364 tables.
VoltBase Pro (voltbase.pro) • Electrical Engineering Reference & Calculation Submittal
Governing Reference: NEC 2023 / IEEE Standard Baseline
Calculated By: __________________________
Reviewed By: __________________________
Approved / Stamped: __________________________

Frequently Asked Questions

How do I choose between 3% and 5% voltage drop?

3% is standard for branch circuits powering sensitive electronics, appliances, and lighting. 5% is the standard total maximum for the entire run from utility entrance to final load.

Related Calculators & Engineering Tools

Voltage Drop Calculator
AWG to mm² Converter
Battery Runtime Calculator
Wire Sizing Reference Guide
Grounding vs. Bonding
How to Size a Wire Properly
Conduit Fill Percentage & Jam Ratio Guide

Educational & Reference Notice: This calculator provides technical estimates based on standard physical formulas. Actual electrical installation, protective device sizing, and conductor selection must be verified against the applicable electrical code (NEC, IEC, CEC) by a licensed electrician or qualified professional engineer.

VoltBasePRO

Fast, practical electrical calculators, conversions, engineering charts, and technical reference tools.

Free Engineering Utilities

Calculators

  • Ohm's Law
  • Voltage Drop
  • Wire Sizing
  • Battery Runtime
  • Solar Array Sizing
  • Breaker Sizing
  • View All 20+ →

Converters & Charts

  • AWG to mm²
  • Watts to Amps
  • kW to HP
  • AWG Wire Table
  • Battery SoC Chart
  • Resistor Color Code

Reference & Guides

  • All Articles & Guides →
  • Master Formulas
  • Grounding vs Bonding
  • 3-Phase Motor Sizing
  • Transformer Sizing
  • Conduit Fill Guide
  • Unit Converter Tool

Platform & Standards

  • About VoltBase Pro
  • Editorial Guidelines
  • Calculation Methodology
  • Engineering Disclaimer
  • Contact & Peer Review
  • Privacy Policy
  • Terms of Use
  • HTML Sitemap

Engineering Disclaimer: Calculations, estimations, formulas, and charts provided on VoltBase Pro are intended solely for educational, reference, and informational purposes. Real-world electrical installations must comply with local electrical codes (e.g. NEC, IEC, CEC) and should always be verified by a licensed electrician or professional electrical engineer.

© 2026 VoltBase Pro. All rights reserved.

Calculated in your browser. Verified against NEC 2023 tables.