Watts to VA Converter (W to Volt-Amps)

Convert real power in watts to apparent power in VA using the load power factor. The correct way to size a UPS, generator or inverter.

Convert Watts to Volt-Amps

W
0.1 - 1.0

1.0 for heaters and incandescent lights; 0.8 is typical for motors and computers with older PSUs.

Conversion Result

Apparent Power in Volt-Amps (VA)
1,250 VA

1.25 kVA, the rating a UPS, generator or inverter must meet

Extra Capacity Needed vs Watts
+25%

The gap between VA and W is the power factor penalty

Step-by-Step Engineering Calculation

  1. 1Apparent power: VA=1000 W0.8=1250.00 VA\text{VA} = \frac{1000\text{ W}}{0.8} = \mathbf{1250.00\text{ VA}} (1.250 kVA)
  2. 2Size generators, UPS units and inverters from the VA figure, not the watt figure, whenever the load power factor is below 1.0.

Conversion Formula & Relationship

VA = W / PF

Generators, UPS units and inverters are rated in VA, but loads are labeled in watts. Dividing watts by the power factor gives the apparent power the source must actually deliver.

Standard Conversion Example

Input: 1,000 W at PF 0.8
Result: 1,250 VA

A 1,000 W motor load with a 0.8 power factor needs a source rated at least 1,250 VA. A 1,000 VA UPS would be overloaded even though the watt number looks equal.

1,000 W at PF 0.8 = 1,250 VA

Quick Reference Conversion Table

Watts (W)Volt-Amps (VA)Common Application / Context
500 W @ PF 1.0500 VAResistive heater load
500 W @ PF 0.8625 VATypical motor / PC load
1,000 W @ PF 0.81,250 VASize a 1500 VA UPS for headroom
2,000 W @ PF 0.92,222 VAModern PFC power supplies
5,000 W @ PF 0.86,250 VAWorkshop / well pump circuit

Frequently Asked Questions

Why is VA always equal to or bigger than watts?

Watts count only the power that does work. VA also includes reactive power that motors and transformers circulate. The ratio between them is the power factor, which is 1.0 at best, so VA can only equal or exceed W.

What power factor should I use if I do not know it?

Use 0.8 for mixed motor and electronic loads, 0.9 or higher for modern equipment with power factor correction, and 1.0 only for purely resistive loads like heaters and incandescent lamps.