kVA Calculator (Amps, kW and kVA for Single & Three-Phase)

Convert between kVA, amps and kW for single-phase and three-phase systems. Built for sizing transformers, generators and services.

kVA
V
0.1 - 1.0

kVA and Amps do not depend on PF. PF only converts between kVA and kW.

kVA Conversion Results

Apparent Power (S)
100 kVA

Three-phase at 480 V

Line Current (I)
120.28 A
Real Power (P)
80 kW

At power factor 0.8

Step-by-Step Engineering Calculation

  1. 1Apparent power: S=100 kVAS = 100\text{ kVA}S=100 kVA at 480 V480\text{ V}480 V (3-Phase)
  2. 2Current: I=100×10003×480=120.28 AI = \frac{100 \times 1000}{\sqrt{3} \times 480} = \mathbf{120.28\text{ A}}I=3​×480100×1000​=120.28 A
  3. 3Real power at PF 0.8: P=100×0.8=80.00 kWP = 100 \times 0.8 = \mathbf{80.00\text{ kW}}P=100×0.8=80.00 kW

Formula & Theory

S (kVA) = (√3 × V × I) / 1000 (3-Phase) | S (kVA) = (V × I) / 1000 (1-Phase) | P (kW) = S × PF

Apparent power in kVA is what transformers, generators and UPS units are rated in. Three-phase kVA uses the line-to-line voltage with the √3 factor; real power in kW follows from the power factor.

Variable Definitions
S:
Apparent Power (kVA) – Total power the source must deliver, including reactive power
P:
Real Power (kW) – Power that does actual work, equal to kVA × PF
V:
Voltage (Volts (V)) – Line-to-line voltage for three-phase, line voltage for single-phase
I:
Current (Amperes (A)) – Line current drawn at the stated voltage
PF:
Power Factor (Ratio (0 to 1)) – Only needed to convert between kVA and kW

Worked Engineering Example

100 kVA Transformer at 480 V

A 100 kVA three-phase transformer secondary at 480 V, feeding a load with 0.8 power factor.

Inputs:
  • Apparent Power: 100 kVA
  • Voltage: 480 V
  • Power Factor: 0.8
Result: Current = 120.28 A, Real Power = 80.00 kW

Key Assumptions

  • •Balanced three-phase load (equal current on all three phases).
  • •Voltage entered for three-phase is the line-to-line value.
  • •Power factor is constant at the operating point.

Limitations & Safety Scope

  • •Unbalanced loads need per-phase calculation; the largest phase current governs equipment sizing.
  • •Transformer kVA ratings also carry temperature-rise and altitude limits this calculator does not model.
VoltBase Pro (voltbase.pro) • Electrical Engineering Reference & Calculation Submittal
Governing Reference: NEC 2023 / IEEE Standard Baseline
Calculated By: __________________________
Reviewed By: __________________________
Approved / Stamped: __________________________

Frequently Asked Questions

How many amps is 100 kVA at 480 V three-phase?

I = (100 × 1000) / (√3 × 480) = 120.28 A. The same transformer at 208 V would deliver 277.6 A, which is why higher voltages are used for large loads.

What is the difference between kVA and kW?

kW is real power that does work. kVA is apparent power, which adds the reactive power motors and transformers circulate. They are equal only at a power factor of 1.0; at PF 0.8 a load needs 1.25 kVA for every 1 kW.

How do I size a transformer from a kW load?

Divide the kW load by the power factor to get kVA, then choose the next standard transformer size above that figure and add headroom for future load growth.

Related Calculators & Engineering Tools

Power Factor Calculator
Power Calculator
Motor Current Calculator
Watts to VA Converter
VA to Watts Converter
Watts to Amps Converter
Master Electrical Formulas

Educational & Reference Notice: This calculator provides technical estimates based on standard physical formulas. Actual electrical installation, protective device sizing, and conductor selection must be verified against the applicable electrical code (NEC, IEC, CEC) by a licensed electrician or qualified professional engineer.

VoltBasePRO

Fast, practical electrical calculators, conversions, engineering charts, and technical reference tools.

Free Engineering Utilities

Calculators

  • Ohm's Law
  • Voltage Drop
  • Wire Sizing
  • Battery Runtime
  • Solar Array Sizing
  • Breaker Sizing
  • View All 20+ →

Converters & Charts

  • AWG to mm²
  • Watts to Amps
  • kW to HP
  • AWG Wire Table
  • Battery SoC Chart
  • Resistor Color Code

Reference & Guides

  • All Articles & Guides →
  • Master Formulas
  • Grounding vs Bonding
  • 3-Phase Motor Sizing
  • Transformer Sizing
  • Conduit Fill Guide
  • Unit Converter Tool

Platform & Standards

  • About VoltBase Pro
  • Editorial Guidelines
  • Calculation Methodology
  • Engineering Disclaimer
  • Contact & Peer Review
  • Privacy Policy
  • Terms of Use
  • HTML Sitemap

Engineering Disclaimer: Calculations, estimations, formulas, and charts provided on VoltBase Pro are intended solely for educational, reference, and informational purposes. Real-world electrical installations must comply with local electrical codes (e.g. NEC, IEC, CEC) and should always be verified by a licensed electrician or professional electrical engineer.

© 2026 VoltBase Pro. All rights reserved.

Calculated in your browser. Verified against NEC 2023 tables.